The fridge controller was on the internet

The fridge controller was on the internet

On the night of 11–12 October 2026, somebody reached into the refrigeration control systems of French supermarkets and changed the settings. Display cases were forced into defrost, setpoints were rewritten, and in the morning staff found cabinets full of spoiled food.

There is no CVE here. No malware, no ransom note, nobody claiming it. The French CERT's alert names no vulnerability, no firmware version and no indicators of compromise. What it names is the thing that made it possible, and the sentence is almost boring: "De manière générale l'exposition d'une interface de gestion sur Internet est contraire aux bonnes pratiques." Generally speaking, exposing a management interface on the internet is contrary to good practice.

That is the entire finding.

What happened, with the numbers attributed properly

The figures in circulation disagree, so here is where each comes from.

France's finance minister Roland Lescure told Parliament on 13 October that about 700 supermarkets were affected, out of roughly 10,000 nationwide. Reuters counted at least 350. Adding up what the chains themselves said — Les Mousquetaires, Carrefour, Coopérative U, Monoprix, E.Leclerc — lands somewhere around 400 to 500. The 700 is a government statement to parliament, not a measured scan result, and it is worth saying so.

The 50°C figure everyone quotes comes from Les Mousquetaires, which owns Intermarché, not from any authority. It said refrigerated display units at around 150 of its stores were switched into defrost and reached as high as 50°C for six hours, and that it discarded all the food involved. CERT-FR publishes no temperature figure at all.

One detail from Le Monde is more instructive than the temperature: attackers extended some defrost cycles from one hour to eight, which delays the alarms. Somebody understood the equipment.

The Paris prosecutor opened an investigation on its own initiative. As of now there is no attribution, no claim of responsibility and no ransom demand.

The equipment

CERT-FR's affected list is four product families, and it is short enough to quote whole: Copeland xweb, Danfoss AK-SC series, Danfoss AK-SM series, Dixell xweb.

The support status is the uncomfortable part. Danfoss declared the AK-SM 800 end of life in May 2021, and the AK-SC 255 and AK-SC 355 were phased out in 2016. Its own October 2025 product bulletin lists a much longer set of hardware under a "hard End of Service policy for legacy products that have already reached their End of Life" — AK-SM 800, AK-SM 350, AK-SM 720, the PI series, AKM, AKA, AK-SC 255, AK-SC 355, EM 100, AK-CS and EM 800. That document says the policy is "driven by recent European cybersecurity legislation."

Danfoss said of this incident that "the majority of units affected were legacy products or current products running outdated firmware." The current-generation AK-SM 800A units that were hit were running old firmware — so this is not purely a museum problem.

On the Copeland and Dixell side, the vendor bulletin of 14 October acknowledges the issue in a discontinued generation: "Nous reconnaissons l'existence de la vulnérabilité identifiée sur une génération de contrôleurs XWEB EVO dont la commercialisation est arrêtée et qui est parvenue en fin de vie." XWEB EVO is end of service and gets no more security fixes; XWEB PRO is the supported platform, and the same bulletin adds that XWEB PRO itself must not be exposed to the internet.

Then there is the line that explains a great deal: "Les XWEB PRO et EVO sont livrés avec le même compte d'usine : identifiant « Admin », mot de passe « Admin »." Both ship with the same factory account, username Admin, password Admin.

Nobody has established that default credentials were used in this attack. But they are documented, and the equipment was reachable.

Was there a vulnerability?

Research exists, and it is worth keeping separate from the incident.

Claroty's Team82 published work in August 2026 on the current AK-SM 800A, finding a hidden "code-of-the-day" authentication path where the device validates a password generated internally from its own current date and time (CVE-2025-41450, CVSS 8.2, fixed in R4.2), a post-authentication command injection via the alarm email configuration (CVE-2025-41451, fixed in R4.3.1), and a configuration-injection denial of service (CVE-2025-41452). Claroty's own caveats matter: that was laboratory research on the current model, it describes no attacks, and it does not cover the AK-SM 800 or AK-SC 355. Synacktiv published a similar date-derived login bypass on the older models back in 2023, unfixed because they are end of life.

A source close to the French prime minister said ANSSI had found a flaw in Danfoss software and contacted the vendor. No CVE was named and nobody has said it was used here.

The practitioners quoted in the French press were unimpressed. Clément Domingo told RMC the operation was not especially sophisticated, blaming skipped updates and "a password that was simply the current date." Ken Munro of Pen Test Partners told Reuters: "This is about basic cyber hygiene," and that it could be "kids messing around."

How to check your own

This is the part that generalises beyond supermarkets, because the pattern — a contractor installs equipment, publishes its management interface so they can support it remotely, and nobody who owns the building ever learns it is there — is not specific to refrigeration.

Do not start with a port list. The Danfoss AK-SM 800A documentation gives HTTPS on 443 and HTTP on 80, both marked user-configurable, plus UDP 5136 for SNMP, 1041 for PI-200 and 5003/5005 for host communication. Because the web ports are configurable, and older guides even suggested moving them, a scan of the obvious ports will miss a relocated interface. Copeland publishes no port numbers for XWEB at all.

Dixell's own check is better, and it needs no tools: from a connection outside the site network — a phone with Wi-Fi switched off works — put the site's public IP address into a browser. The XWEB login page must not appear. If it does, you have found the problem.

For a wider estate, the fingerprint to look for is the Danfoss StoreView page title on newer units, or a Flash loader page on the older AK-SM 800.

The scale of the exposure, by several independent counts: IPinfo found 2,528 of these systems worldwide and 1,331 in France on 6–7 October, of which 85% ran software with known flaws and 527 were unsupported models. Predicta Lab counted 2,752 worldwide and 1,590 in France. Reuters cited Shodan at over 4,500. By 14 October only 316 of IPinfo's French 1,331 were still answering — a 76% drop, which is what a national alert looks like in telemetry.

A factory reset is not enough

This is the sharpest line in either alert, and both authorities make it.

CERT-FR: "N'effectuer qu'un Reset Factory est dans ce cas insuffisant, les persistances d'une instance compromise seront supprimées mais l'équipement restera vulnérable et sera certainement de nouveau compromis." A factory reset removes the attacker's persistence but leaves the device vulnerable, and it will certainly be compromised again.

Romania's DNSC says the same in its own alert: "O simplă resetare la setările din fabrică (Factory Reset) nu este suficientă, aceasta eliminând mecanismele de persistență, însă echipamentul rămâne vulnerabil."

The order that actually works, from both: remove the internet exposure first, then reset, then restore access only through a secure VPN or protected network, then reconfigure. CERT-FR permits firewall IP filtering of the refrigeration contractor's source addresses as an emergency measure but is explicit that it "ne doit pas être considérée comme pérenne" — not a permanent solution.

One operational warning that is easy to skip: check your insurance contract terms before cutting the data feed to your refrigeration service provider. Both CERT-FR and DNSC put that step ahead of pulling the plug. And Copeland's recovery procedure ends by telling you to physically verify the temperatures in the cabinets, because altered setpoints and alarm thresholds are a food safety problem, not just a security one.

Romania got its own alert

DNSC published an alert on 14 October 2026 listing the identical four product families. It recommends restricting internet access to the equipment, verifying the full configuration and especially the defrost programmes, moving remote access behind a secure VPN, and for Danfoss specifically: update firmware to the latest version, set the security level to "Strict", and verify that default passwords have been changed.

It also notes plainly what the French alert does not contain: "alerta CERT-FR nu specifică versiunile afectate și nu include identificatori CVE sau indicatori de compromitere (IoC)." And it cites Law 58/2023, article 5(a) — responsibility for the security of a system sits with its owner, administrator or user. Not with the contractor who installed it.

Worth being accurate here: the DNSC alert does not say there have been Romanian victims, and it does not say there have not been. It says the equipment is out there.

The general version

Every organisation has some equipment it did not install, does not administer and cannot name. Building management, cameras, badge readers, HVAC, a UPS with a web interface. Somebody set it up, published it so they could reach it, and left.

The question is not whether you trust that contractor. It is whether you know what is answering on your own public addresses. That part is checkable from the outside in an afternoon — a ClickScan external scan enumerates what responds, and what it checks covers the services and interfaces nobody meant to publish. Where it needs a person, ClickSecure AI's expert services cover that.

Sources: CERT-FR alert CERTFR-2026-ALE-012 · DNSC alert, 14 October 2026 · Copeland/Dixell XWEB security bulletin · Danfoss end of service bulletin · Claroty Team82 research, August 2026 · IPinfo exposure analysis

The 700 figure is the French finance minister's statement to Parliament; other counts range from 350 upward and no authority has published a verified total. The 50°C and six-hour figures are Les Mousquetaires' own account, not an authority's. No CVE has been linked to this incident by any authority, and the initial access vector, the exploited flaw if any, and the attacker remain unestablished. The Claroty CVEs are prior laboratory research on a different model and are not evidence of the attack path. Exposure counts come from four different scanning methodologies and are not comparable with each other.